AWC C-205 Low pH Membrane Cleaning Compound
CHEMICAL FEEDING AND CONTROL:
Use potable water that is free of residual chlorine or other oxidizing agents to make the cleaning solution. The cleaning solution is prepared by addition of 8-10 lb of AWC C-205 for every 100 gallons of water (~1 wt% Solution). Add caustic soda or ammonium hydroxide in small increments until pH is between 2–3. The cleaning solution is then circulated throughout the system without exceeding pressures, temperatures and flow rates recommended by the membrane manufacturer. Cleaning efficacy can be further improved by heating the cleaning solution and alternately circulating the solution for 15 minutes and then soaking
the membranes for 15 minutes. This should be repeated as many times as necessary. AWC C-205 should be added as necessary to the cleaning solution to maintain the pH range of 2–3 throughout the entire cleaning process. Depending on severity of fouling, your AWC representative will recommend optimal cleaning times.
ADVANTAGES
• Low pH membrane-cleaning compound for
dissolution of carbonate and phosphate scales
• Effectively dissolves and chelates iron, aluminum
and other metal oxides
• Chelates light deposits of pH independent
precipitants such as calcium fluoride, calcium
sulfate, barium sulfate and strontium sulfate
• Compatible with all Thin Film Composite R.O.
membranes from all major membrane suppliers
• Certified by NSF to NSF/ANSI Standard 60
PACKAGING
50 lb. pails and 400 lb. non-returnable plastic
drums